TECHNICAL DATA
| Power supply | 10..30 Vdc (R203-2-L-U) 90..264 Vac (50-60 Hz) (R203-2-H-U) |
| Consumption | 2.8 W |
| Isolation | 3,500 Vac (to/from power-supply circuits) 1,500 Vac (other circuits) |
| Status indicators | Input / output status, IO address status, wiring error, Ethernet data transit/connection |
| Installation category | 600 V CAT III |
| Programming | Web server, DIP switch |
| Accuracy class | 0.2% for voltage/current; 0.5% for power |
| Flash memory | 8 MB |
| Special Network functions | Dual Daisy Chain Ethernet connection LAN fault bypass |
| Special functions | No. 2 digital inputs @5kHz |
| Connection type / Connection mode | Single-phase, three-phase 3-wire, three-phase 4-wire, CT, CT with mV output, Rogowski transducers, Aron |
| Protection rating | Front IP20 |
| Mounting | 35 mm DIN rail |
| Connections | screw terminals |
| Operating temperature | -25..+65°C |
| Dimensions | 107x90x32 mm |
| Weight | 170 g |
| Enclosure | UL94-V0 self-extinguishing PC/ABS, black |
| Voltage/Current Inputs | |
| Phase-voltage measurement | Voltage: up to 600 Vac, freq. 45 ÷ 65 Hz VT with output up to 600 Vac relative to neutral |
| Phase-current measurement | CT with 1-5 A FS output CT with mV output or Rogowski up to 250 mV |
| INTEGRATED I/O | |
| Digital inputs | No. 2, activated by voltage from 12 to 24V, with 5kHz digital counters |
| Digital outputs | No. 2, Imax capacity = 50 mA Vmax = 28V |
| analog outputs | No. 1 configurable for voltage 0..10 Vdc, min load resistance 2kΩ or current 0..20, 4..20 mA, max load resistance 500Ω Transmission error: 0,1% of max range Thermal drift: 100 ppm/K |
| COMMUNICATION | |
| Ports | No.2 Ethernet 100 Mbps |
| Protocols | OPC UA server |
| Connections | Ethernet switch with Daisy Chain protection |
Manuals, flyers
Firmwares
DRAWINGS & CAD MODELS
Product Compliance
Accessories
Related Products
Product versions
Power analyzer with universal input and OPC UA server protocol (power supply 230V)
Power analyzer with universal input and OPC UA server protocol (power supply 24V)
Accessories
Rogowski sensor L=180 cm, internal Ø 57 cm, 100mV/1KA-50Hz and cable L=3mt
Split-core current transformer 100/5A CL.0,5 D=20x30mm
Split-core current transformer 250/5A CL.0,5 D=20x30mm
Split-core current transformer 400/5A CL.0,5 D=20x30mm
Split-core current transformer 400/5A CL.0,5 D=50x80mm
Split-core current transformer 500/5A CL.0,5 D=50x80mm
Split-core current transformer 600/5A CL.0,5 D=50x80mm
Split-core current transformer 750/5A CL.0,5 D=50x80mm
Split-core current transformer 800/5A CL.0,5 D=80x80mm
Split-core current transformer 1000/5A CL.0,5 D=80x80mm
Busbar-through current transformer 50/5A CL.1, 22mm cable, busbar 30x10mm
Busbar-through current transformer 60/5A CL.1, 22mm cable, busbar 30x10mm
Busbar-through current transformer 100/5A CL.1, 22mm cable, busbar 30x10mm
Busbar-through current transformer 150/5A CL.1, 22mm cable, busbar 30x10mm
Busbar-through current transformer 100/5A CL.0,5, 32mm cable
Busbar-through current transformer 400/5A CL.0,5, 32mm cable