TECHNICAL DATA
Code: | K400CL |
Description: | Surge protection for analog signals and logical , slim format . 6.2mm |
IEC category / EN type | C1, C2, C3, D1 |
Rated surge arrester voltage UC | 25 VAC / 36 VDC |
Lightning test current Iimp (10/350)μs | 500 A |
Nominal current IN | 350 mA (40°C) |
Nominal discharge current In (8/20)μs | 10 kA |
Residual surge current (8/20)μs Line - ground | 20 kA |
Output voltage limitatin at 1 kV/μs - Line-line/line-ground | ≤ 60 V / ≤ 650 V |
Max. back-up fuse (in acc. with IEC 127-2/III) | 315 mA |
Resistance per path | 3,3 Ω ± 20% |
Temperature range | -40 °C ... 80 °C |
Degree of protection in acc. with CEI/EN 60539 | IP 20 |
Inflammability class in acc. with UL94 | V0 |
Test standards | DIN EN 61643-21:2012 |
Connection data (Solid / stranded / AWG ) | 0,2-2,5 mm2 / 0,2-2,5 mm2 / 24-14 |
Thread | M 3 |
Torque | 0,8 Nm |
Stripping length | 8 mm |
Contamination class | 2 |
Surge voltage category | III |
Max. input voltage Ui / Uo | 36 V DC |
Max.input current Ii / Io (see item 7) | T6: 150 mA / T5: 200 mA / T4: 350 mA |
Max. internal capacitance Ci / Co | 1,3 nF |
Max. inner inductance Li / Lo | 1 μH |
Max. inner power Pi / Po | 3 W |
Maximum inner time factor t (Ri/Li) | 0,2 μs |
SHIPPING AND EXPORT INFORMATION
PRODUCT CODE | K400CL |
GROSS WEIGHT kg | 0.065 |
ORIGIN | DE |
CN (Combined Nomenclature) | 85363030 |
ECCN | EAR99 |
SENECA offices will be closed from 23 December to 7 January included. Business activities will resume regularly on Monday 8 January. To guarantee you a punctual shipment of products by Thursday 21 December (the last day of shipping), we kindly ask you to send any requests no later than Wednesday 20 December. Orders received from December 21st will be dispatched from January 8th. We wish you happy winter holidays!
Product versions
K400CL-10 - 10pc SPD 25VAC/36VDC,C1/2/3/D1, LOOP mA/0-10V/DIGIT
Availability to confirm, please contact us ?