TECHNICAL DATA
Code: | K400CL |
Description: | Surge protection for analog signals and logical , slim format . 6.2mm |
IEC category / EN type | C1, C2, C3, D1 |
Rated surge arrester voltage UC | 25 VAC / 36 VDC |
Lightning test current Iimp (10/350)μs | 500 A |
Nominal current IN | 350 mA (40°C) |
Nominal discharge current In (8/20)μs | 10 kA |
Residual surge current (8/20)μs Line - ground | 20 kA |
Output voltage limitatin at 1 kV/μs - Line-line/line-ground | ≤ 60 V / ≤ 650 V |
Max. back-up fuse (in acc. with IEC 127-2/III) | 315 mA |
Resistance per path | 3,3 Ω ± 20% |
Temperature range | -40 °C ... 80 °C |
Degree of protection in acc. with CEI/EN 60539 | IP 20 |
Inflammability class in acc. with UL94 | V0 |
Test standards | DIN EN 61643-21:2012 |
Connection data (Solid / stranded / AWG ) | 0,2-2,5 mm2 / 0,2-2,5 mm2 / 24-14 |
Thread | M 3 |
Torque | 0,8 Nm |
Stripping length | 8 mm |
Contamination class | 2 |
Surge voltage category | III |
Max. input voltage Ui / Uo | 36 V DC |
Max.input current Ii / Io (see item 7) | T6: 150 mA / T5: 200 mA / T4: 350 mA |
Max. internal capacitance Ci / Co | 1,3 nF |
Max. inner inductance Li / Lo | 1 μH |
Max. inner power Pi / Po | 3 W |
Maximum inner time factor t (Ri/Li) | 0,2 μs |
SHIPPING AND EXPORT INFORMATION
PRODUCT CODE | K400CL |
GROSS WEIGHT kg | 0.065 |
ORIGIN | DE |
CN (Combined Nomenclature) | 85363030 |
ECCN | EAR99 |