TECHNICAL DATA
| Code: | S400CL-1 |
| Description: | Overvoltage protection for analog signals and logical with isolator |
| IEC category / VDE requirement class | C1, C2, C3, D1 |
| Max. perm. operating voltage UC | 30 VDC / 21 VAC |
| Lightning test current Iimp (10/350) μs - Core - ground | 500 A |
| Nominal current IN | 300 mA (40 °C) |
| Backup fuse max. | 315 mA |
| Nominal discharge surge current In (8/20) μs - Core – core / core - ground | 5 kA / 5 kA |
| Total surge current (8/20) μs - Core – ground | 10 kA |
| Output voltage threshold at 1 kV / μs - Core – core / core – ground | ≤ 45 V / ≤ 650 V |
| Residual voltage at In core - core | ≤ 45 V |
| Protection level UP C2 ( 10kV / 5 kA ) - Core – core / core – ground | ≤ 55 V / ≤ 650 V |
| Response time TA Core – core / core - ground | ≤ 1 ns / ≤ 100 ns |
| Cut-off frequency (3dB) symmetrical in a 150 Ω system | typ. 2 MHz |
| Resistance per path | 3,3 Ù ±20% |
| Temperature range | -40 °C…+85 °C |
| Inflammability class according to UL 94 | V0 |
| Degree of protection with IEC 60529 / EN 60529 | IP20 |
| Test standards | IEC 61 643-21:2002-03 |
| Connection data (solid / stranded / AWG) | 0,2 mm² - 2,5 mm² / 0,2 mm² - 2,5 mm² / 24-12 |
| Screw thread / tightening torque | M3 / 0,6 Nm |
| Stripping length | 8 mm |
| Surge voltage category | III |
| Pollution degree | 2 |
SHIPPING AND EXPORT INFORMATION
| PRODUCT CODE | S400CL-1 |
| GROSS WEIGHT kg | 0.105 |
| ORIGIN | DE |
| CN (Combined Nomenclature) | 85363030 |
| ECCN | EAR99 |
Manuals, flyers
Installation Manual
SHA256 Checksum:
78474df88f3c0ebc3a0462f9bc69518ecafe6b63654a632cab3430f852c216f2
SHA256 Checksum:
78474df88f3c0ebc3a0462f9bc69518ecafe6b63654a632cab3430f852c216f2

EN

Contact us for