TECHNICAL DATA

Protection Electrical Data (L-N / N-PE / L-PEN)  
IEC test class / EN type C1 / C2 / C3 / D1
Rated voltage UN 24 Vdc
Max. permanent voltage UC 30 Vdc / 21 Vac
Rated leakage current In (8/20)µs 5 kA
Max. Leakage current Imax (8/20)µs 20 kA
Atmospheric test current Iimp (10/350) µs per conductor 0.5 kA
Protection Level Up (conductor-to-conductor)
≤ 55 V (C1 - 1 kV / 500 A)
≤ 65 V (C2 - 10 kV / 5 kA)
≤ 50 V (C3 - 25 A)
(conductor-to-ground)
≤ 55 V (C3 - 100 A)
≤ 750 V (C1 - 1 kV / 500 A)
≤ 750 V (C2 - 10 kV / 5 kA)
≤ 700 V (C3 - 25 A)
≤ 750 V (C3 - 100 A)
(conductor-ground)
≤ 50 V (C1 - 1 kV / 500 A)
≤ 65 V (C2 - 10 kV / 5 kA)
(conductor-ground)
≤ 750 V (C1 - 1 kV / 500 A)
≤ 750 V (C2 - 10 kV / 5 kA)
General Data  
Max. fuse for standard wiring 630 mA (FF)
Frequency limit fg (3dB) symmetrical in 50 Ohm system tip. 940 kHz
Resistance per conductor 1.65 Ohm ±20 %
Dimensions (wxhxd) 6.2 x 105 x 83 mm
Temperature range -40..+70°C
Grade of Protection IP20
Combustibility Class by UL 94 V0
Casing material PBT
Connection interface Connection push-in
Approvals CE

SHIPPING AND EXPORT INFORMATION

PRODUCT CODE S400CL-1-N
GROSS WEIGHT kg 0.105
ORIGIN DE
CN (Combined Nomenclature) 85363030
ECCN EAR99

Manuals, flyers

 
IT EN FR DE ES RU
Installation Manual
pdf icon it pdf icon en pdf icon fr pdf icon de pdf icon es -
Surge Protections Devices - S400
pdf icon it pdf icon en - - - pdf icon ru

Certifications

 
CE Declaration of conformity
pdf icon Multi
REACH and ROHS declarations
pdf icon Multi
Customs codes
pdf icon Multi
0
0
0

Product versions

Price
S400CL-1-N

SPD with built-in status indicator and knife disconnect for a 2-wire potential-free signal circuit

In stock ?
51.00

Accessories

Price
S400CL-1-P

Final closing form S400CL-1

Availability to confirm, please contact us ?
0.70