TECHNICAL DATA
Protection Electrical Data (L-N / N-PE / L-PEN) | |
IEC test class / EN type | C1 / C2 / C3 / D1 |
Rated voltage UN | 24 Vdc |
Max. permanent voltage UC | 30 Vdc / 21 Vac |
Rated leakage current In (8/20)µs | 5 kA |
Max. Leakage current Imax (8/20)µs | 20 kA |
Atmospheric test current Iimp (10/350) µs per conductor | 0.5 kA |
Protection Level Up | (conductor-to-conductor) ≤ 55 V (C1 - 1 kV / 500 A) ≤ 65 V (C2 - 10 kV / 5 kA) ≤ 50 V (C3 - 25 A) (conductor-to-ground) ≤ 55 V (C3 - 100 A) ≤ 750 V (C1 - 1 kV / 500 A) ≤ 750 V (C2 - 10 kV / 5 kA) ≤ 700 V (C3 - 25 A) ≤ 750 V (C3 - 100 A) (conductor-ground) ≤ 50 V (C1 - 1 kV / 500 A) ≤ 65 V (C2 - 10 kV / 5 kA) (conductor-ground) ≤ 750 V (C1 - 1 kV / 500 A) ≤ 750 V (C2 - 10 kV / 5 kA) |
General Data | |
Max. fuse for standard wiring | 630 mA (FF) |
Frequency limit fg (3dB) symmetrical in 50 Ohm system | tip. 940 kHz |
Resistance per conductor | 1.65 Ohm ±20 % |
Dimensions (wxhxd) | 6.2 x 105 x 83 mm |
Temperature range | -40..+70°C |
Grade of Protection | IP20 |
Combustibility Class by UL 94 | V0 |
Casing material | PBT |
Connection interface | Connection push-in |
Approvals | CE |
SHIPPING AND EXPORT INFORMATION
PRODUCT CODE | S400CL-1-N |
GROSS WEIGHT kg | 0.105 |
ORIGIN | DE |
CN (Combined Nomenclature) | 85363030 |
ECCN | EAR99 |
Manuels, prospectus
Certifications
Accessoires
Dear Customer, please note that our offices will be closed from August 8 to August 24 due to the summer holidays. The last shipping day before the break is Wednesday, August 6. We kindly ask you to place any orders by August 5. Orders received after this deadline will be processed starting from Monday, August 25, when regular operations resume. Thank you for your cooperation.