TECHNICAL DATA
| Protection Electrical Data (L-N / N-PE / L-PEN) | |
| IEC test class / EN type | C1 / C2 / C3 / D1 |
| Rated voltage UN | 24 Vdc |
| Max. permanent voltage UC | 30 Vdc / 21 Vac |
| Rated leakage current In (8/20)µs | 5 kA |
| Max. Leakage current Imax (8/20)µs | 20 kA |
| Atmospheric test current Iimp (10/350) µs per conductor | 0.5 kA |
| Protection Level Up | (conductor-to-conductor) ≤ 55 V (C1 - 1 kV / 500 A) ≤ 65 V (C2 - 10 kV / 5 kA) ≤ 50 V (C3 - 25 A) (conductor-to-ground) ≤ 55 V (C3 - 100 A) ≤ 750 V (C1 - 1 kV / 500 A) ≤ 750 V (C2 - 10 kV / 5 kA) ≤ 700 V (C3 - 25 A) ≤ 750 V (C3 - 100 A) (conductor-ground) ≤ 50 V (C1 - 1 kV / 500 A) ≤ 65 V (C2 - 10 kV / 5 kA) (conductor-ground) ≤ 750 V (C1 - 1 kV / 500 A) ≤ 750 V (C2 - 10 kV / 5 kA) |
| General Data | |
| Max. fuse for standard wiring | 630 mA (FF) |
| Frequency limit fg (3dB) symmetrical in 50 Ohm system | tip. 940 kHz |
| Resistance per conductor | 1.65 Ohm ±20 % |
| Dimensions (wxhxd) | 6.2 x 105 x 83 mm |
| Temperature range | -40..+70°C |
| Grade of Protection | IP20 |
| Combustibility Class by UL 94 | V0 |
| Casing material | PBT |
| Connection interface | Connection push-in |
| Approvals | CE |
SHIPPING AND EXPORT INFORMATION
| PRODUCT CODE | S400CL-1-N |
| GROSS WEIGHT kg | 0.105 |
| ORIGIN | DE |
| CN (Combined Nomenclature) | 85363030 |
| ECCN | EAR99 |
Manuels, prospectus
Conformité des produits
Accessoires
☀️ Summer Holiday Closure 🏖️ Our offices will be closed from August 7 to 23 inclusive.To guarantee the shipment of your products before our shutdown, we kindly ask you to submit your orders according to the following deadlines:
- Non-EU Destinations: Orders must be received by 11:00 AM (CET) on Tuesday, August 4th.
- EU Destinations: Orders must be received by 11:00 AM (CET) on Wednesday, August 5th.
Versions du produit
Prix
€ 51,00
Accessoires
Prix
€ 0,70

FR

Ecrivez-nous pour