TECHNICAL DATA
| Protection Electrical Data (L-N / N-PE / L-PEN) | |
| IEC test class / EN type | C1 / C2 / C3 / D1 |
| Rated voltage UN | 24 Vdc |
| Max. permanent voltage UC | 30 Vdc / 21 Vac |
| Rated leakage current In (8/20)µs | 5 kA |
| Max. Leakage current Imax (8/20)µs | 20 kA |
| Atmospheric test current Iimp (10/350) µs per conductor | 0.5 kA |
| Protection Level Up | (conductor-to-conductor) ≤ 55 V (C1 - 1 kV / 500 A) ≤ 65 V (C2 - 10 kV / 5 kA) ≤ 50 V (C3 - 25 A) (conductor-to-ground) ≤ 55 V (C3 - 100 A) ≤ 750 V (C1 - 1 kV / 500 A) ≤ 750 V (C2 - 10 kV / 5 kA) ≤ 700 V (C3 - 25 A) ≤ 750 V (C3 - 100 A) (conductor-ground) ≤ 50 V (C1 - 1 kV / 500 A) ≤ 65 V (C2 - 10 kV / 5 kA) (conductor-ground) ≤ 750 V (C1 - 1 kV / 500 A) ≤ 750 V (C2 - 10 kV / 5 kA) |
| General Data | |
| Max. fuse for standard wiring | 630 mA (FF) |
| Frequency limit fg (3dB) symmetrical in 50 Ohm system | tip. 940 kHz |
| Resistance per conductor | 1.65 Ohm ±20 % |
| Dimensions (wxhxd) | 6.2 x 105 x 83 mm |
| Temperature range | -40..+70°C |
| Grade of Protection | IP20 |
| Combustibility Class by UL 94 | V0 |
| Casing material | PBT |
| Connection interface | Connection push-in |
| Approvals | CE |
SHIPPING AND EXPORT INFORMATION
| PRODUCT CODE | S400CL-1-N |
| GROSS WEIGHT kg | 0.105 |
| ORIGIN | DE |
| CN (Combined Nomenclature) | 85363030 |
| ECCN | EAR99 |
Handbücher, Flyer
Zertifizierungen
Dear Customer, please note that our offices will be closed from December 24 to January 6 inclusive due to the winter holidays. The last shipping day before the break is Monday, 22nd. We kindly ask you to place any orders by December 18th. Orders received after this date may only be processed when operations resume on 7 January. Thank you for your cooperation.