TECHNICAL DATA

Code: K400CL
Description: Surge protection for analog signals and logical , slim format . 6.2mm
IEC category / EN type C1, C2, C3, D1
Rated surge arrester voltage UC 25 VAC / 36 VDC
Lightning test current Iimp (10/350)μs 500 A
Nominal current IN 350 mA (40°C)
Nominal discharge current In (8/20)μs 10 kA
Residual surge current (8/20)μs Line - ground 20 kA
Output voltage limitatin at 1 kV/μs - Line-line/line-ground ≤ 60 V / ≤ 650 V
Max. back-up fuse (in acc. with IEC 127-2/III) 315 mA
Resistance per path 3,3 Ω ± 20%
Temperature range -40 °C ... 80 °C
Degree of protection in acc. with CEI/EN 60539 IP 20
Inflammability class in acc. with UL94 V0
Test standards DIN EN 61643-21:2012
Connection data (Solid / stranded / AWG ) 0,2-2,5 mm2 / 0,2-2,5 mm2 / 24-14
Thread M 3
Torque 0,8 Nm
Stripping length 8 mm
Contamination class 2
Surge voltage category III
Max. input voltage Ui / Uo 36 V DC
Max.input current Ii / Io (see item 7) T6: 150 mA / T5: 200 mA / T4: 350 mA
Max. internal capacitance Ci / Co 1,3 nF
Max. inner inductance Li / Lo 1 μH
Max. inner power Pi / Po 3 W
Maximum inner time factor t (Ri/Li) 0,2 μs

SHIPPING AND EXPORT INFORMATION

PRODUCT CODE K400CL
GROSS WEIGHT kg 0.065
ORIGIN DE
CN (Combined Nomenclature) 85363030
ECCN EAR99

Manuels, prospectus

 
IT EN RU
Surge Protections Devices - S400
- pdf icon it pdf icon en pdf icon ru
Manuel d'Installation
pdf icon Multi - - -

DESIGNS & CAD MODÈLES

 
3D Model
stp icon Multi

Certifications

 
Déclaration de conformité CE
pdf icon Multi
REACH and ROHS declarations
pdf icon Multi
Customs codes
pdf icon Multi
0
0
0

Versions du produit

K400CL

K400CL - SPD 25VAC/36VDC,C1/2/3/D1, LOOP mA / 0-10V / DIGIT

Disponibilité à confirmer, nous contacter ?
K400CL-10

K400CL-10 - 10pc SPD 25VAC/36VDC,C1/2/3/D1, LOOP mA/0-10V/DIGIT

Disponibilité à confirmer, nous contacter ?