TECHNICAL DATA

Accuracy class 0,5
Transformation ratio depending on the model:
100/5
150/5
200/5
250/5
300/5
400/5
Rated burden  1,5 VA
Secondary current  5A
Frequency  40-60 Hz
Rated dynamic current DC 2,5 I.ter@1s
Rated thermal current DC 40-80 IpN@1s
Reference voltage  0,72 kV
Test voltage 3kV@50Hz (1 min)
Continuous overcurrent 1,2 In
Safety factor (FS) =<5
Operating temperature  -25..+50°C
Storage temperature -40..+80°C
Maximum feed-through cable temperature 70°C
Relative humidity 90% non-condensing
Air insulation Class E
Protection rating IP30 (CEI EN 60529)
Enclosure Self-extinguishing ABS, protected terminals
Installation type DIN rail
Cut-out dimensions 36x37 mm
Dimensions 89x111x40 mm
Weight 720 g
Reference standards CEI 38-1, IEC 185, VDE 0414, EN600044-1, EN60044-1A

Manuals, flyers

 
IT EN
Datasheet
pdf icon it pdf icon en

Product Compliance

 
▼
REACH and ROHS declarations
pdf icon Multi
Customs codes
pdf icon Multi

Related Products

0
0
0

Product versions

Price
TAA-01005-3637

Split core current transformer 100/5A CL.0,5 D=36x37mm

In stock ?
€ 95.00