TECHNICAL DATA
| Protection Electrical Data (L-N / N-PE / L-PEN) | |
| IEC test class / EN type | C1 / C2 / C3 / D1 |
| Rated voltage UN | 24 Vdc |
| Max. permanent voltage UC | 30 Vdc / 21 Vac |
| Rated leakage current In (8/20)µs | 5 kA |
| Max. Leakage current Imax (8/20)µs | 20 kA |
| Atmospheric test current Iimp (10/350) µs per conductor | 0.5 kA |
| Protection Level Up | (conductor-to-conductor) ≤ 55 V (C1 - 1 kV / 500 A) ≤ 65 V (C2 - 10 kV / 5 kA) ≤ 50 V (C3 - 25 A) (conductor-to-ground) ≤ 55 V (C3 - 100 A) ≤ 750 V (C1 - 1 kV / 500 A) ≤ 750 V (C2 - 10 kV / 5 kA) ≤ 700 V (C3 - 25 A) ≤ 750 V (C3 - 100 A) (conductor-ground) ≤ 50 V (C1 - 1 kV / 500 A) ≤ 65 V (C2 - 10 kV / 5 kA) (conductor-ground) ≤ 750 V (C1 - 1 kV / 500 A) ≤ 750 V (C2 - 10 kV / 5 kA) |
| General Data | |
| Max. fuse for standard wiring | 630 mA (FF) |
| Frequency limit fg (3dB) symmetrical in 50 Ohm system | tip. 940 kHz |
| Resistance per conductor | 1.65 Ohm ±20 % |
| Dimensions (wxhxd) | 6.2 x 105 x 83 mm |
| Temperature range | -40..+70°C |
| Grade of Protection | IP20 |
| Combustibility Class by UL 94 | V0 |
| Casing material | PBT |
| Connection interface | Connection push-in |
| Approvals | CE |
SHIPPING AND EXPORT INFORMATION
| PRODUCT CODE | S400CL-1-N |
| GROSS WEIGHT kg | 0.105 |
| ORIGIN | DE |
| CN (Combined Nomenclature) | 85363030 |
| ECCN | EAR99 |
Manuals, flyers
Certifications
Accessories
🎄 Holiday Notice. Our offices will be closed from December 24 to January 6. All orders placed from December 23 onward will be processed and shipped starting from January 7. Thank you for your understanding, and happy holidays from the entire SENECA team!
Product versions
Price
S400CL-1-N
SPD with built-in status indicator and knife disconnect for a 2-wire potential-free signal circuit
In stock ?
€ 51.00
Accessories
Price
€ 0.70

EN

Contact us for