TECHNICAL DATA
Power supply | 7..30 Vdc (da loop 4..20 mA) |
Hot swapping | Yes |
Max power consumption | 24 mA |
Max power dissipation | < 660 mW |
Insulation | 1,5 kVac (2 vie) |
Status LED | Anomaly Alarm |
Accuracy Class | 0,1% |
Input type | Cu50, Cu100 Pt100, Pt500, Pt1000 Ni100, Ni120, Ni1000 TC J, K, R, S, T, B, E, N, L; input impedance 10 MΩ Potentiometer: 500 Ω..100 kΩ Voltage: -150..+150 mV; input impedance 10 MΩ Voltage: -30..+30 V; input impedance 200 kΩ Current: -24..+24mA; impedance 40Ω Resistance 0..+400 (1.760) Ω |
Output channel | Current 4-20 mA (passive) |
Filter | Additional for reading stabilization |
Special functions | Cold junction compensation Insertable filter Output reversal |
A/D conversion | 16 bit |
Thermal drift | <120 ppm/K |
Connection | 8 spring clamps |
Rejection | 50 o 60 Hz (programmable) |
Programming | EASY SETUP |
Insulation technique | Digital / Optocoupler |
Processing | 32 bit floating point calculation |
Protection degree | IP20 |
Housing | PBT, nero |
Dimension (WxHxD) | 6,2x93,1x102,5 mm |
Weight | 45 g |
Operating temperature | -20..+65°C |
Standard | CE |
Norms | EN 61000-6-4, EN 61010-6-2, EN 61010-1 |
SHIPPING AND EXPORT INFORMATION
PRODUCT CODE | K121 |
GROSS WEIGHT kg | 0.075 |
ORIGIN | IT |
CN (Combined Nomenclature) | 85437090 |
ECCN | EAR99 |
Manuals, flyers
DRAWINGS & CAD MODELS
Certifications
Accessories required for product configuration
Dear Customer, please note that our offices will be closed from August 8 to August 24 due to the summer holidays. The last shipping day before the break is Wednesday, August 6. We kindly ask you to place any orders by August 5. Orders received after this deadline will be processed starting from Monday, August 25, when regular operations resume. Thank you for your cooperation.
Product versions
Price
€ 90.00
K121-C
Loop powered isolator / universal converter - presetted version (please specify configuration settings in order notes)
In stock ?
€ 104.00
Accessories required for product configuration
Price
€ 74.00
€ 180.00