TECHNICAL DATA

Coil length From 30 to 300 cm (internal Ø up to ~57cm)
Cord diameter 12,4 ±0,2 mm
Output level (RMS) 333 mV / kA @50Hz
Transducer resistance From 300 to 2000 Ω
Position error Better than ±1% of reading
Operating voltage 1000 VRMS CAT III; 600 VRMS CAT IV
Test voltage 7400 VRMS / 1 min
Operating temperature From -30°C to +80°C
Protection rating IP67

SHIPPING AND EXPORT INFORMATION

PRODUCT CODE RC190-030-333-3M
GROSS WEIGHT kg 0.17
ORIGIN IT
CN (Combined Nomenclature) 85437090
ECCN EAR99