TECHNICAL DATA
Power supply | 11..40 Vdc; 19..28 Vac, 50–60 Hz |
Power consumption | 3,8 W (typical) |
Isolation | 1,5 kVac |
Status LED indicators | Power supply Ethernet links and data traffic Data transmission/reception on serial ports Power supply / M-BUS communication Data transmission/reception on M-BUS port |
Web Server authentication | Yes |
Password | Yes |
Protection degree | IP20 |
Operating temperature | -25..+65°C |
Ethernet port | 1 Fast Ethernet 10/100 baseTx, RJ45 frontal |
Serial port | 1 RS485 COM#1 port for IDC10 connector Baud rate from 1,200 to 115,200 bps |
M-BUS port | 1 M-BUS port 25 M-BUS slave nodes max Baud rate 300 to 38,400 bps |
Supported protocols | Modbus RTU Slave, Modbus TCP-IP server (max simultaneous 8 clients) |
N° Max Client TCP-IP (Server Mode) | 8 |
N° Max Client variabili / Tag | 500 |
N° Max Modbus registers | 1000 |
N° Max Nodi Slave Modbus RTU/ASCII | 128 |
DIP switch | Yes |
Configuration | Via built-in Web Server |
Web server | Yes, Reading statuses (max. 50 tags per page), settings, M-BUS devices, M-BUS network scan, Setup Tag, firmware update, and database |
SDD (Seneca Discovery Device) | Yes |
Connections | Screw terminals, 7-way extractable screw, pitch 5 mm Screw terminals, 2-way removable screw, 5 mm pitch Ethernet connector |
Dimension (WxHxD) | 53,3 x 90 x 32,2 mm |
Weight | 80 g |
Housing | PC / ABS self-extinguishing UL94-V0 |
Installation | On DIN rail IEC EN 60715 or wall-mounted |
Certification | CE |
Norms | EN61000-6-4, EN 61000-6-2, EN 61010-1, EN 60950 |
Related Products
SENECA offices will be closed from 23 December to 7 January included. Business activities will resume regularly on Monday 8 January. To guarantee you a punctual shipment of products by Thursday 21 December (the last day of shipping), we kindly ask you to send any requests no later than Wednesday 20 December. Orders received from December 21st will be dispatched from January 8th. We wish you happy winter holidays!