TECHNICAL DATA

Power supply 5..30 Vdc (loop powered)
Response time <220 ms (<620 ms with rejection 50-60 Hz)
Accuracy Class 0,1%
Input channel • Pt100
Standard: EN 60751/A2 (ITS-90)
Measuring range: -200..+650°C
Minimum Span: 20°C
2,3,4-wire connection
• Ni100
Measuring range: -60..+650°C
Minimum Span: 20°C
2,3,4-wire connection
Output channel CURRENT (mA) 4..20, 20..4 mA (2-wire)
Thermal drift < 100 ppm (30 ppm tipical)
Programming EASY SETUP software (programming kit: start / end of scale measurement, connection and RTD type, rejection, measurement filter, cable resistance, fault / over-range output)
Operating temperature -40..+85°C
Connections Spring clamps
Dimension (ØxH) Ø 43,7 x 20 mm
Standard CE
Norms EN 61000-6-4, EN 61000-6-2

SHIPPING AND EXPORT INFORMATION

PRODUCT CODE T120
GROSS WEIGHT kg 0.034
ORIGIN IT
TARIC 85437090
ECCN EAR99

Handbücher, Flyer

 
IT EN FR DE ES
Trasmettitori di temperatura Serie T
pdf icon it pdf icon en - - -
Installation Manual
pdf icon it pdf icon en pdf icon fr pdf icon de pdf icon es

Zertifizierungen

 
Multi
Konformitätserklärung
pdf icon Multi
Dichiarazione REACH e ROHS
pdf icon Multi
Dichiarazione di origine
pdf icon Multi
0
0
0

Produktversionen

Preis
T120

2 wire loop powered transmitter for Pt100 and Ni100 probes

Auf Lager ?
42,00
T120-C

[T120-C] - presetted version (please specify configuration settings in order notes)

Auf Lager ?
50,00

Zubehörs

Preis
EASY-USB

USB - UART TTL converter

In begrenzter Menge verfügbar ?
72,00
S117P1

RS232/USB, TTL/USB, RS485/USB serial converter

Auf Lager ?
152,00
FLEX-DIN

DIN rail adapter for T120 and T121

In begrenzter Menge verfügbar ?
5,00