TECHNICAL DATA
Power supply | 5..30 Vdc (loop powered) |
Response time | <220 ms (<620 ms with rejection 50-60 Hz) |
Accuracy Class | 0,1% |
Input channel | • Pt100 Standard: EN 60751/A2 (ITS-90) Measuring range: -200..+650°C Minimum Span: 20°C 2,3,4-wire connection • Ni100 Measuring range: -60..+650°C Minimum Span: 20°C 2,3,4-wire connection |
Output channel | CURRENT (mA) 4..20, 20..4 mA (2-wire) |
Thermal drift | < 100 ppm (30 ppm tipical) |
Programming | EASY SETUP software (programming kit: start / end of scale measurement, connection and RTD type, rejection, measurement filter, cable resistance, fault / over-range output) |
Operating temperature | -40..+85°C |
Connections | Spring clamps |
Dimension (ØxH) | Ø 43,7 x 20 mm |
Standard | CE |
Norms | EN 61000-6-4, EN 61000-6-2 |
SHIPPING AND EXPORT INFORMATION
PRODUCT CODE | T120 |
GROSS WEIGHT kg | 0.034 |
ORIGIN | IT |
CN (Combined Nomenclature) | 85437090 |
ECCN | EAR99 |
Manuels, prospectus
DESIGNS & CAD MODÈLES
Certifications
Accessoires
Accessoires nécessaires pour la configuration du produit
Produits Liés
SENECA offices will be closed from August 3 to August 25 included. Business activities will resume regularly on Monday 26 August. Orders received from July 30 will be shipped from August 26. We wish you happy summer holiday!
Versions du produit
[T120-C] - presetted version (please specify configuration settings in order notes)
En stock ?