TECHNICAL DATA
Power supply | 5..30 Vdc (loop powered) |
Response time | <220 ms (<620 ms with rejection 50-60 Hz) |
Accuracy Class | 0,1% |
Input channel | • Pt100 Standard: EN 60751/A2 (ITS-90) Measuring range: -200..+650°C Minimum Span: 20°C 2,3,4-wire connection • Ni100 Measuring range: -60..+650°C Minimum Span: 20°C 2,3,4-wire connection |
Output channel | CURRENT (mA) 4..20, 20..4 mA (2-wire) |
Thermal drift | < 100 ppm (30 ppm tipical) |
Programming | EASY SETUP software (programming kit: start / end of scale measurement, connection and RTD type, rejection, measurement filter, cable resistance, fault / over-range output) |
Operating temperature | -40..+85°C |
Connections | Spring clamps |
Dimension (ØxH) | Ø 43,7 x 20 mm |
Standard | CE |
Norms | EN 61000-6-4, EN 61000-6-2 |
SHIPPING AND EXPORT INFORMATION
PRODUCT CODE | T120 |
GROSS WEIGHT kg | 0.034 |
ORIGIN | IT |
CN (Combined Nomenclature) | 85437090 |
ECCN | EAR99 |