TECHNICAL DATA

Code S400HV-2
Description Type 2 surge arrester for power lines
IEC category / EN type II , T2 / T2
Number of ports 1
Nominal voltage UN AC 240/415 VAC (TN-S) / 240/415 V AC (TT)
Maximum continuous operating voltage UC - L-N / N-PE 335 V AC / 260 V AC
Residual current IPE ≤ 5 μA
Short-circuit current rating ISCCR 25 kA
Follow current interrupt rating Ifi - N-PE 100 A (260 V)
Max. discharge surge current Imax (8/20)μs - L-N / N-PE 40 kA / 40 kA
Voltage protection level UP L-N / N-PE ≤ 1,5 kV / 1,5 kV
Nominal discharge surge current In (8/20)μs - L-N / N-PE 20 kA / 20 kA
Max. required backup fuse with branch wiring 125 A AC (gG)
Max. required backup fuse with V-type through wiring 80 A AC (gG)
Ambient temperature (operation) -40 °C ... 80 °C
Permissible humidity (operation) 5 % ... 95 %
Degree of protection IP 20

SHIPPING AND EXPORT INFORMATION

PRODUCT CODE S400HV-2
GROSS WEIGHT kg 0.105
CN (Combined Nomenclature) 85363030
ECCN EAR99

Handbücher, Flyer

 
IT EN RU
Surge Protections Devices - S400
pdf icon it pdf icon en pdf icon ru
Installationsanleitung
pdf icon it pdf icon en -

Zertifizierungen

 
CE-Konformitätserklärung
pdf icon Multi
REACH and ROHS declarations
pdf icon Multi
Customs codes
pdf icon Multi
0
0
0
Dear Customer, please note that our offices will be closed from August 8 to August 24 due to the summer holidays. The last shipping day before the break is Wednesday, August 6. We kindly ask you to place any orders by August 5. Orders received after this deadline will be processed starting from Monday, August 25, when regular operations resume. Thank you for your cooperation.

 

Produktversionen

Preis
S400HV-2

SPD 230VAC, no FM contact, tipe 2 with 3 conductors

Auf Lager ?
103,00

Zubehörs

Preis
S400HV-2-RIC-SL

Replacement plug 1 LN / PE S400HV-2, no contact FMII / T2 335Vac / 260Vac

In begrenzter Menge verfügbar ?
71,00
S400HV-2-RIC-SN

Replacement plug N / per S400HV2 II / T2 335 VAC / 260 VAC / -335 Vac / 260Vac

In begrenzter Menge verfügbar ?
61,00