TECHNICAL DATA

Code S400HV-2
Description Type 2 surge arrester for power lines
IEC category / EN type II , T2 / T2
Number of ports 1
Nominal voltage UN AC 240/415 VAC (TN-S) / 240/415 V AC (TT)
Maximum continuous operating voltage UC - L-N / N-PE 335 V AC / 260 V AC
Residual current IPE ≤ 5 μA
Short-circuit current rating ISCCR 25 kA
Follow current interrupt rating Ifi - N-PE 100 A (260 V)
Max. discharge surge current Imax (8/20)μs - L-N / N-PE 40 kA / 40 kA
Voltage protection level UP L-N / N-PE ≤ 1,5 kV / 1,5 kV
Nominal discharge surge current In (8/20)μs - L-N / N-PE 20 kA / 20 kA
Max. required backup fuse with branch wiring 125 A AC (gG)
Max. required backup fuse with V-type through wiring 80 A AC (gG)
Ambient temperature (operation) -40 °C ... 80 °C
Permissible humidity (operation) 5 % ... 95 %
Degree of protection IP 20

SHIPPING AND EXPORT INFORMATION

PRODUCT CODE S400HV-2
GROSS WEIGHT kg 0.105
CN (Combined Nomenclature) 85363030
ECCN EAR99

Handbücher, Flyer

 
IT EN RU
Surge Protections Devices - S400
- pdf icon it pdf icon en pdf icon ru
Installationsanleitung
pdf icon Multi - - -

Zertifizierungen

 
CE-Konformitätserklärung
pdf icon Multi
Dichiarazione REACH e ROHS
pdf icon Multi
0
0
0

Dear Customers and Business Partners, we inform you that SENECA offices are closed from 6th to 21st August. Orders received during the closing period will be handled when business resumes on Monday 22nd August. Thank you for your attention and we wish you a happy summer break. SENECA staff

Produktversionen

Preis
S400HV-2

SPD 230VAC, no FM contact, tipe 2 with 3 conductors

Auf Lager ?
74,00

Zubehörs

Preis
S400HV-2-RIC-SL

Replacement plug 1 LN / PE S400HV-2, no contact FMII / T2 335Vac / 260Vac

In begrenzter Menge verfügbar ?
39,00
S400HV-2-RIC-SN

Replacement plug N / per S400HV2 II / T2 335 VAC / 260 VAC / -335 Vac / 260Vac

In begrenzter Menge verfügbar ?
45,00