TECHNICAL DATA
| Power supply | 7..30 Vdc (da loop 4..20 mA) |
| Hot swapping | Yes |
| Max power consumption | 24 mA |
| Max power dissipation | < 660 mW |
| Insulation | 1,5 kVac (2 vie) |
| Status LED | Anomaly Alarm |
| Accuracy Class | 0,1% |
| Input type | Cu50, Cu100 Pt100, Pt500, Pt1000 Ni100, Ni120, Ni1000 TC J, K, R, S, T, B, E, N, L; input impedance 10 MΩ Potentiometer: 500 Ω..100 kΩ Voltage: -150..+150 mV; input impedance 10 MΩ Voltage: -30..+30 V; input impedance 200 kΩ Current: -24..+24mA; impedance 40Ω Resistance 0..+400 (1.760) Ω |
| Output channel | Current 4-20 mA (passive) |
| Filter | Additional for reading stabilization |
| Special functions | Cold junction compensation Insertable filter Output reversal |
| A/D conversion | 16 bit |
| Thermal drift | <120 ppm/K |
| Connection | 8 spring clamps |
| Rejection | 50 o 60 Hz (programmable) |
| Programming | EASY SETUP |
| Insulation technique | Digital / Optocoupler |
| Processing | 32-bit floating-point calculation |
| Protection degree | IP20 |
| Housing | PBT, nero |
| Dimension (WxHxD) | 6,2x93,1x102,5 mm |
| Weight | 45 g |
| Operating temperature | -20..+65°C |
| Standard | CE, ATEX |
| Norms | EN 61000-6-4, EN 61010-6-2, EN 61010-1 |
SHIPPING AND EXPORT INFORMATION
| PRODUCT CODE | K121 |
| GROSS WEIGHT kg | 0.075 |
| ORIGIN | IT |
| CN (Combined Nomenclature) | 85437090 |
| ECCN | EAR99 |
Handbücher, Flyer
ZEICHNUNGEN & CAD MODELLE
Zertifizierungen
Erforderliches Zubehör für die Produktkonfiguration
Produktversionen
Preis
€ 90,00
K121-C
[K121-C] Loop powered isolator / universal converter - presetted version (please specify configuration settings in order notes)
Auf Lager ?
€ 104,00
Erforderliches Zubehör für die Produktkonfiguration
Preis
€ 74,00
€ 180,00

DE

Schreiben Sie uns für