TECHNICAL DATA
| Power Supply | 10..40 Vdc; 19..28 Vac |
| Max Consumption | 5,6 W |
| Max Isolation | 1.5 kVac |
| Status Indicators | Power supply Input / Output status STS (IP address / DHCP) RX / TX (Receive/transmit data over RS485) Ethernet TRF / LNK (Transit packets / Ethernet connection) |
| Protection Degree | IP20 |
| Operating temperature | -25..+65°C |
| Dimensions (WxHxD) | 106 x 90 x 32 mm |
| Weight | 170 g |
| Housing | Pc/ABS material self-extinguishing UL94-V0, black color |
| Connections | 3.5mm pitch terminals, and double RJ45 connector |
| Mounting | On DIN EN 60715 rail, wall-mounted / panel-mounted |
| Programming | Integrated web server, DIP-switch |
| Special Features | Double Ethernet Daisy Chain connection LAN fault bypass (the active connection between the two Ethernet ports of the device in case of power failure) Modbus Passthrough (TCP-IP to RS485) IP, MAC, Firmware identification, and configuration by SDD tool |
| Interfaces | Nr.2 Ethernet ports (with LAN fault-bypass function) 100 baseT on RJ45 - 100 Mbps (TCP-IP) Nr.1 RS485 port on terminals M23-M24-M25 - 115.200 bps (RS485) |
| Protocols | ModBUS RTU, ModBUS TCP-IP, HTTP |
| Cable for Ethernet communication between devices | CAT5 or CAT5e unshielded |
| ModBUS Communication | Up to 64 nodes without repeater and max speed 115 kbps |
| ANALOG OUTPUT CHANNELS | |
| Number of Channels | 4 Analog |
| Type and Range | Voltage (±10 V) or current (0..20 mA); |
| DIGITAL INPUT/OUTPUT CHANNELS | |
| Number of Channels | 8 Digital Inputs/Outputs |
| Type and Range | Inputs = voltage: ON threshold: > 11 V; OFF threshold: < 4 V; Vmax: 24 V; Impedance: 9 kΩ Outputs = MOSFET, PNP; max. voltage/current: 0.2 A ; 12..24 V |
| STANDARD | |
| Certifications | CE |
| Homologations and Standards | EN61000-6-4, EN61000-6-2, EN61010-1 |