R-PASS features a widget-based data display interface that facilitates alarm management, command sending and chart display through an HTML5 web browser. The device is fully configured via the web server, eliminating the need for expensive development environments.
TECHNICAL DATA
| Power supply | 10..40 Vdc; 19..28 Vac |
| Power consumption | 8 W |
| Isolation | 1.500 Vac, 3-way |
| Protection rating | IP20 |
| Operating temperature | -25..+65 °C |
| Connections | 3,5 mm pitch terminals Micro USB connector RJ45 connector (x4) |
| Digital inputs | Number of channels: 4 Current draw: 2,2mA Input voltage: 0..30V, ON threshold > 9V, OFF threshold < 8V Compliant with IEC6113-2 Type 1 & 3 |
| analog inputs | Number of channels: 2 Voltage 0..30Vdc, impedance 20kΩ Current 0..25mA, impedance ~50Ω |
| Digital outputs | Number of channels: 4 OptoMOS® 30Vdc, max. 25mA |
| Dimensions (wxhxd) | 106 x 90 x 32 mm |
| Weight | 170 g |
| Enclosure | UL94-V0 self-extinguishing PC / ABS material, black colour |
| Installation | On DIN EN 60715 rail, wall / panel mounting |
| Marking / Certifications | CE |
| Ethernet ports | No.2 Fast Ethernet 10/100Tx ports (1 LAN, 1 WAN) on RJ45 |
| Serial ports | No.1 RS232/RS485 port on terminals, max baud rate 115kbps No.1 RS485 port on terminals, max baud rate 115kbps |
| WiFi module | Wi-Fi 802.11 b/g/n 2.4 GHz (optional) |
| USB ports | No.1 full USB host port |
| Modem | Optional R-COMM module |
| Industrial / IT protocols | ModBUS TCP-IP Server/Client, ModBUS RTU Master/Slave, FTP/FTPs Client, FTP/ sFTP Server, HTTP/HTTPS server, SMTP |
| IoT protocols | MQTT, OPC UA Server, http post |
| Security protocols | OpenVPN, SSL |
| Operating modes | ModBUS Gateway (Ethernet - Serial, shared memory, transparent Gateway, serial tunnelling) IoT/Cloud-based gateway Datalogger Alarm management unit Serial sniffer Redundant network unit Remote assistance/remote control VPN module Logic unit LAN/WAN separator |
| Connectivity | Max 32 Modbus TCP-IP Clients (Server Mode), 2000 client variables (tags), 128 MobBUS RTU/ASCII Slave Nodes, Max 25 Modbus TCP Servers (Client mode), 1 / 496 VPN Clients, NAT 1:1, Static Router |
| Programming | EASY SETUP 2,Web Server |
| VPN management software | VPN BOX Manager, OpenVPN, VPN Client Communicator |
| Network management tool | SDD (Seneca Discovery Device), SESC (Seneca Ethernet to Serial Connection) |
| If-Then-Else logic | Yes |
| IoT support and third-party platforms | Cloud BOX, LET'S, MQTT, OPC UA Server |