TECHNICAL DATA
Code: | S400NET-1 |
Description: | Surge protection for Ethernet , serial and fieldbus , 5 wires |
IEC test classification | C1,C2,C3,D1 |
Nominal voltage IN | 12 Vdc |
Maximum continuous operating voltage UC | 9,8 Vac / 14 Vdc |
Nominal current IN | 450 mA (45 °C) |
Impulse discharge current Iimp (10/350)μs per path | 2,5 kA |
Nominal discharge current In (8/20)μs - Core-Core / Core-Ground | 10 kA / 10 kA |
Total surge current (8/20)μs | 20 kA |
Voltage protection level UP - Core-Core / Core-Ground | ≤ 50V (C3 - 25 A) / ≤ 50 V (C3 - 25 A) |
Output voltage limitation at 1 kV/μs, static - Core-Core / Core-Ground | ≤ 25 V/≤ 25 V |
Resistance in series | 2,2 Ω ±10 % |
Max. required back-up fuse | 500 mA |
Ambient temperature (operation) | -40°C..+85°C |
Degree of protection | IP20 |
Inflammability class according to UL 94 | V0 |
Pollution degree | 2 |
Surge voltage category | III |
Test standards | IEC 61643-21/A1 / EN 61643-21/A1 |
SHIPPING AND EXPORT INFORMATION
PRODUCT CODE | S400NET-1 |
GROSS WEIGHT kg | 0.105 |
ORIGIN | DE |
CN (Combined Nomenclature) | 85363030 |
ECCN | EAR99 |
Manuales, flyer
Certificados
SENECA offices will be closed from 23 December to 7 January included. Business activities will resume regularly on Monday 8 January. To guarantee you a punctual shipment of products by Thursday 21 December (last day of shipping), we kindly ask you to send any requests no later than Wednesday 20 December. Orders received from December 21st will be dispatched from January 8th.
While thanking you for your cooperation, we wish you a happy winter holidays!
Versiones del producto
Aaccesorios
Spare plug for S400NET-1 C1/C2/C3/D1 5.2 VDC / 3.6 VAC
Disponibilidad para confirmar, contáctenos ?