TECHNICAL DATA

Code S400LV-1
Description Type 3 surge protection for power equipment
Test classification // EN type III / T3
Number of ports One
Nominal voltage UN 24 V AC (TN-S)
Nominal frequency 50 Hz (60 Hz)
Maximum continuous operating voltage UC 34 V AC / 34 V DC
Combination wave UOC 2 kV
Protection level UP - L-N / L-PE / N-PE ≤ 0,18 kV / ≤ 0,55 kV / ≤ 0,55 kV
Residual current IPE ≤ 5 μA
Nominal discharge current In (8/20) μs 1 kA
Short-circuit current rating ISCCR 1,5 kA AC / 1 kA DC
Rated load current IL at 63 °C 16 A AC
Max. backup fuse with branch wiring 16 A AC (B) / 10 A DC (gG) / 10 A DC (B)
Maximum backup fuse for through wiring 16 A AC (B) / 10 A DC (gG) / 10 A DC (B)
Ambient temperature (operation) -40 °C ... 80 °C
Degree of protection IP20

SHIPPING AND EXPORT INFORMATION

PRODUCT CODE S400LV-1
GROSS WEIGHT kg 0.105
ORIGIN DE
CN (Combined Nomenclature) 85363030
ECCN EAR99

Manuales, flyer

 
IT EN RU
Surge Protections Devices - S400
- pdf icon it pdf icon en pdf icon ru
Manual de instalación
pdf icon Multi - - -

Certificados

 
Declaración de conformidad CE
pdf icon Multi
REACH and ROHS declarations
pdf icon Multi
Customs codes
pdf icon Multi
0
0
0

SENECA offices will be closed from August 3 to August 25 included. Business activities will resume regularly on Monday 26 August. Orders received from July 30 will be shipped from August 26. We wish you happy summer holiday!

Versiones del producto

S400LV-1

SPD 34 VAC/44 VDC, TIPO III, CONT. FM, 3F.(L,N,PE)

Disponibilidad para confirmar, contáctenos ?

Aaccesorios

S400LV-1-RIC-SL

Replacement plug 24VAC / DC S400LV-1, with contact FM III / T3 24 VAC / DC

Disponibilidad para confirmar, contáctenos ?