TECHNICAL DATA
| Code: | K400CL |
| Description: | Surge protection for analog signals and logical , slim format . 6.2mm |
| IEC category / EN type | C1, C2, C3, D1 |
| Rated surge arrester voltage UC | 25 VAC / 36 VDC |
| Lightning test current Iimp (10/350)μs | 500 A |
| Nominal current IN | 350 mA (40°C) |
| Nominal discharge current In (8/20)μs | 10 kA |
| Residual surge current (8/20)μs Line - ground | 20 kA |
| Output voltage limitatin at 1 kV/μs - Line-line/line-ground | ≤ 60 V / ≤ 650 V |
| Max. back-up fuse (in acc. with IEC 127-2/III) | 315 mA |
| Resistance per path | 3,3 Ω ± 20% |
| Temperature range | -40 °C ... 80 °C |
| Degree of protection in acc. with CEI/EN 60539 | IP 20 |
| Inflammability class in acc. with UL94 | V0 |
| Test standards | DIN EN 61643-21:2012 |
| Connection data (Solid / stranded / AWG ) | 0,2-2,5 mm2 / 0,2-2,5 mm2 / 24-14 |
| Thread | M 3 |
| Torque | 0,8 Nm |
| Stripping length | 8 mm |
| Contamination class | 2 |
| Surge voltage category | III |
| Max. input voltage Ui / Uo | 36 V DC |
| Max.input current Ii / Io (see item 7) | T6: 150 mA / T5: 200 mA / T4: 350 mA |
| Max. internal capacitance Ci / Co | 1,3 nF |
| Max. inner inductance Li / Lo | 1 μH |
| Max. inner power Pi / Po | 3 W |
| Maximum inner time factor t (Ri/Li) | 0,2 μs |
SHIPPING AND EXPORT INFORMATION
| PRODUCT CODE | K400CL |
| GROSS WEIGHT kg | 0.065 |
| ORIGIN | DE |
| CN (Combined Nomenclature) | 85363030 |
| ECCN | EAR99 |
Manuels, prospectus
Manuel d'Installation
SHA256 Checksum:
d170034896861c959a8c16305613a3ae8a49fb8fe3280bdef66434077f0fb88e
SHA256 Checksum:
d170034896861c959a8c16305613a3ae8a49fb8fe3280bdef66434077f0fb88e
DESIGNS & CAD MODÈLES
3D Model
Certifications
Produits alternatifs
Dear Customer, please note that our offices will be closed from December 24 to January 6 inclusive due to the winter holidays. The last shipping day before the break is Monday, 22nd. We kindly ask you to place any orders by December 18th. Orders received after this date may only be processed when operations resume on 7 January. Thank you for your cooperation.
Versions du produit
K400CL
K400CL - SPD 25VAC/36VDC,C1/2/3/D1, LOOP mA / 0-10V / DIGIT
Disponibilité à confirmer, nous contacter ?
K400CL-10
K400CL-10 - 10pc SPD 25VAC/36VDC,C1/2/3/D1, LOOP mA/0-10V/DIGIT
Disponibilité à confirmer, nous contacter ?
FR

Ecrivez-nous pour