TECHNICAL DATA
| Power supply | 7..30 Vdc (da loop 4..20 mA) |
| Hot swapping | Yes |
| Max power consumption | 24 mA |
| Max power dissipation | < 660 mW |
| Insulation | 1,5 kVac (2 vie) |
| Status LED | Anomaly Alarm |
| Accuracy Class | 0,1% |
| Input type | Cu50, Cu100 Pt100, Pt500, Pt1000 Ni100, Ni120, Ni1000 TC J, K, R, S, T, B, E, N, L; input impedance 10 MΩ Potentiometer: 500 Ω..100 kΩ Voltage: -150..+150 mV; input impedance 10 MΩ Voltage: -30..+30 V; input impedance 200 kΩ Current: -24..+24mA; impedance 40Ω Resistance 0..+400 (1.760) Ω |
| Output channel | Current 4-20 mA (passive) |
| Filter | Additional for reading stabilization |
| Special functions | Cold junction compensation Insertable filter Output reversal |
| A/D conversion | 16 bit |
| Thermal drift | <120 ppm/K |
| Connection | 8 spring clamps |
| Rejection | 50 o 60 Hz (programmable) |
| Programming | EASY SETUP |
| Insulation technique | Digital / Optocoupler |
| Processing | 32-bit floating-point calculation |
| Protection degree | IP20 |
| Housing | PBT, nero |
| Dimension (WxHxD) | 6,2x93,1x102,5 mm |
| Weight | 45 g |
| Operating temperature | -20..+65°C |
| Standard | CE, ATEX |
| Norms | EN 61000-6-4, EN 61010-6-2, EN 61010-1 |
SHIPPING AND EXPORT INFORMATION
| PRODUCT CODE | K121 |
| GROSS WEIGHT kg | 0.075 |
| ORIGIN | IT |
| CN (Combined Nomenclature) | 85437090 |
| ECCN | EAR99 |
Manuels, prospectus
DESIGNS & CAD MODÈLES
Certifications
Accessoires nécessaires pour la configuration du produit
🎄 Holiday Notice. Our offices will be closed from December 24 to January 6. All orders placed from December 23 onward will be processed and shipped starting from January 7. Thank you for your understanding, and happy holidays from the entire SENECA team!
Versions du produit
Prix
€ 90,00
K121-C
[K121-C] Loop powered isolator / universal converter - presetted version (please specify configuration settings in order notes)
En stock ?
€ 104,00
Accessoires nécessaires pour la configuration du produit
Prix
€ 74,00
€ 180,00

FR

Ecrivez-nous pour