TECHNICAL DATA
Precision Class | 1 |
Transformation Ratio | 50/5 |
Nominal power output | 1 VA |
Secondary current | 5A |
Frequency | 40-60 Hz |
Nominal dynamic DC | 2.5 I.ter@1s |
Nominal thermal current dc | 40-80 IpN@1s |
Reference voltage | 0.72 kV |
Test voltage | 3kV@50Hz (1 min) |
Permanent overcurrent | 1.2 In |
Safety factor (FS) | =<5 |
Temperature of use | -25..+50°C |
Storage temperature | -40..+80°C |
Max. through-wire temperature | 70°C |
Relative humidity | 90% non-condensing |
Isolation in air | Class E |
Protection class | IP30 (CEI EN 60529) |
Container | Self-extinguishing ABS, sealable terminal covers |
Installation type | DIN rail |
Hole dimensions | 22 mm (cable), 30x10 mm (bar) |
Dimensions | 46x57x83.5 mm |
Weight | n.a. |
Reference standards | CEI 38-1, IEC 185, VDE 0414, EN600044-1, EN60044-1A |