Code: |
K400CL |
Description: |
Surge protection for analog signals and logical , slim format . 6.2mm |
IEC category / EN type |
C1, C2, C3, D1 |
Rated surge arrester voltage UC |
25 VAC / 36 VDC |
Lightning test current Iimp (10/350)μs |
500 A |
Nominal current IN |
350 mA (40°C) |
Nominal discharge current In (8/20)μs |
10 kA |
Residual surge current (8/20)μs Line - ground |
20 kA |
Output voltage limitatin at 1 kV/μs - Line-line/line-ground |
≤ 60 V / ≤ 650 V |
Max. back-up fuse (in acc. with IEC 127-2/III) |
315 mA |
Resistance per path |
3,3 Ω ± 20% |
Temperature range |
-40 °C ... 80 °C |
Degree of protection in acc. with CEI/EN 60539 |
IP 20 |
Inflammability class in acc. with UL94 |
V0 |
Test standards |
DIN EN 61643-21:2012 |
Connection data (Solid / stranded / AWG ) |
0,2-2,5 mm2 / 0,2-2,5 mm2 / 24-14 |
Thread |
M 3 |
Torque |
0,8 Nm |
Stripping length |
8 mm |
Contamination class |
2 |
Surge voltage category |
III |
Max. input voltage Ui / Uo |
36 V DC |
Max.input current Ii / Io (see item 7) |
T6: 150 mA / T5: 200 mA / T4: 350 mA |
Max. internal capacitance Ci / Co |
1,3 nF |
Max. inner inductance Li / Lo |
1 μH |
Max. inner power Pi / Po |
3 W |
Maximum inner time factor t (Ri/Li) |
0,2 μs |