TECHNICAL DATA
| Code | S400LV-1 |
| Description | Type 3 surge protection for power equipment |
| Test classification // EN type | III / T3 |
| Number of ports | One |
| Nominal voltage UN | 24 V AC (TN-S) |
| Nominal frequency | 50 Hz (60 Hz) |
| Maximum continuous operating voltage UC | 34 V AC / 34 V DC |
| Combination wave UOC | 2 kV |
| Protection level UP - L-N / L-PE / N-PE | ≤ 0,18 kV / ≤ 0,55 kV / ≤ 0,55 kV |
| Residual current IPE | ≤ 5 μA |
| Nominal discharge current In (8/20) μs | 1 kA |
| Short-circuit current rating ISCCR | 1,5 kA AC / 1 kA DC |
| Rated load current IL at 63 °C | 16 A AC |
| Max. backup fuse with branch wiring | 16 A AC (B) / 10 A DC (gG) / 10 A DC (B) |
| Maximum backup fuse for through wiring | 16 A AC (B) / 10 A DC (gG) / 10 A DC (B) |
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Degree of protection | IP20 |
SHIPPING AND EXPORT INFORMATION
| PRODUCT CODE | S400LV-1 |
| GROSS WEIGHT kg | 0.105 |
| ORIGIN | DE |
| CN (Combined Nomenclature) | 85363030 |
| ECCN | EAR99 |