TECHNICAL DATA

Power supply 7..30 Vdc (from 4..20 mA loop)
Hot swapping Yes
Max current consumption 24 mA
Max power dissipation < 660 mW
Isolation  1.5 kVac (2-way)
LED Fault
Alarm
Accuracy class 0,1%
Input type Cu50, Cu100
Pt100, Pt500, Pt1000
Ni100, Ni120, Ni1000
TC J, K, R, S, T, B, E, N, L; input impedance 10 MΩ
Potentiometer: 500 Ω..10 kΩ
Voltage: -150..+150 mV; input impedance 10 MΩ
Voltage: -30..+30 V; input impedance 200 kΩ
Current: -24..+24mA; impedance 40Ω
Resistance 0..+400 (1.760) Ω
Output channel Current 4-20 mA (passive)
Filter Additional filter for reading stabilisation
Special functions Cold-junction compensation
Switchable filter
Output inversion
A/D conversion 16 bit
Thermal drift <120 ppm/K
Connection 8 spring terminals
Rejection 50 or 60 Hz (programmable)
Programming EASY SETUP software
Isolation method Digital / Optocoupler
Processing 32-bit floating-point calculation
Protection rating IP20
Enclosure PBT, black
Dimensions (WxHxD) 6,2x93,1x102,5 mm
Weight 45 g
Operating temperature -20..+65°C
Approvals CE, ATEX
Standards EN 61000-6-4, EN 61010-6-2, EN 61010-1

SHIPPING AND EXPORT INFORMATION

K121
kg 0.075
IT
85437090
ECCN EAR99

 
IT EN FR DE ES
Datasheet
pdf icon it pdf icon en - - -
K-Series converters range flyer
pdf icon it pdf icon en - - -
Installation Manual
pdf icon it pdf icon en pdf icon fr pdf icon de pdf icon es

ЧЕРТЕЖИ И CAD МОДЕЛИ

 
▼
2D model
dwg icon Multi
3D Model
dwg icon Multi
3D Model (electrical symbols)
dwg icon Multi
3D Model
stp icon Multi

 
▼
CE Conformity Declaration
pdf icon Multi
REACH and ROHS declarations
pdf icon Multi
Customs codes
pdf icon Multi
0
0
2

Product versions

Price
K121
Loop powered universal converter
?
€ 93,00
K121-C
[K121-C] Loop powered isolator / universal converter - presetted version (please specify configuration settings in order notes)
?
€ 107,00


Price
EASY-USB
USB - UART TTL converter
?
€ 76,00
S117P1
RS232/USB, TTL/USB, RS485/USB serial converter
?
€ 185,00